CBT cable is an electrical cable with copper conductors, PVC insulation, and a PVC outer sheath. It is designed for use in damp environments where there is no mechanical stress and provides safe power transmission in concealed and surface-mounted electrical installations in residential and commercial buildings.
CBT cable is an electrical cable with copper conductors, PVC insulation, and a PVC outer sheath. It is designed for safe power transmission in residential, commercial, and indoor electrical installations.
Thanks to its PVC-based construction, CBT cable is ideal for both concealed and surface-mounted installations. It provides a practical and reliable solution for damp environments where there is no mechanical stress.
| Nominal Kesit No x mm² |
İletken Çapı mm |
Standart Et Kalınlığı (İzole) mm |
Standart Et Kalınlığı (Kılıf) mm |
Yaklaşık Dış Çap max. mm |
20°C'de Maks. İletken DC Direnci Ω/km |
Yaklaşık Toplam Ağırlık kg/km |
30°C'de Maks. Akım Taşıma Kapasitesi Pipe A - Air A |
|---|---|---|---|---|---|---|---|
| Num. of Cores No x mm² |
Wires Diameter mm |
Thickness of Insulation mm |
Thickness of Sheath mm |
Approx. Overall Diameter max. mm |
Conductor DC Resistance at 20°C Ω/km |
Approx. Total Weight kg/km |
Max. Current Carrying Capacity at 30°C Pipe A - Air A |
| Номинальное сечение No x мм² |
Диаметр жилы мм |
Толщина изоляции мм |
Толщина оболочки мм |
Приблизительный наружный диаметр макс. мм |
Сопротивление проводника при 20°C Ом/км |
Приблизительный общий вес кг/км |
Макс. токовая нагрузка при 30°C Pipe A - Air A |
| 2 x 1 | 1,1 | 0,6 | 1,20 | 7 | 18,1 | 57 | 28 - 19 |
| 2 x 1,5 | 1,35 | 0,7 | 1,20 | 7,8 | 12,1 | 73 | 32 - 20 |
| 2 x 2,5 | 1,73 | 0,8 | 1,20 | 9,2 | 7,41 | 104 | 42 - 27 |
| 2 x 4 | 2,19 | 0,8 | 1,40 | 10,4 | 4,61 | 144 | 54 - 37 |
| 3 x 1 | 1,1 | 0,6 | 1,20 | 7,4 | 18,1 | 75 | 28 - 19 |
| 3 x 1,5 | 1,35 | 0,7 | 1,40 | 8,6 | 12,1 | 105 | 26 - 18 |
| 3 x 2,5 | 1,73 | 0,8 | 1,40 | 10,1 | 7,41 | 151 | 34 - 25 |
| 3 x 4 | 2,19 | 0,8 | 1,40 | 11 | 4,61 | 199 | 44 - 34 |
| 3 x 6 + 4 | 2,68 - 2,19 | 0,8 - 0,8 | 1,40 - 1,40 | 12,8 | 3,08 | 329 | 28 - 19 |
| 4 x 1,5 | 1,35 | 0,7 | 1,40 | 9,3 | 12,1 | 131 | 26 - 18 |
| 4 x 2,5 | 1,73 | 0,8 | 1,40 | 11 | 7,41 | 190 | 34 - 25 |
| 4 x 4 | 2,19 | 0,8 | 1,40 | 12 | 4,61 | 253 | 44 - 34 |
| 4 x 6 | 2,68 | 0,8 | 1,40 | 13,4 | 3,08 | 348 | 56 - 43 |
| 5 x 1,5 | 1,35 | 0,7 | 1,40 | 10,1 | 12,1 | 157 | 32 - 18 |
| 5 x 2,5 | 1,73 | 0,8 | 1,40 | 12 | 7,41 | 229 | 42 - 25 |
| Nominal Kesit No x mm² |
İletken Çapı mm |
Standart Et Kalınlığı (İzole) mm |
Standart Et Kalınlığı (Kılıf) mm |
Yaklaşık Dış Çap max. mm |
20°C'de Maks. İletken DC Direnci Ω/km |
Yaklaşık Toplam Ağırlık kg/km |
30°C'de Maks. Akım Taşıma Kapasitesi Pipe A - Air A |
|---|---|---|---|---|---|---|---|
| Num. of Cores No x mm² |
Wires Diameter mm |
Thickness of Insulation mm |
Thickness of Sheath mm |
Approx. Overall Diameter max. mm |
Conductor DC Resistance at 20°C Ω/km |
Approx. Total Weight kg/km |
Max. Current Carrying Capacity at 30°C Pipe A - Air A |
| Номинальное сечение No x мм² |
Диаметр жилы мм |
Толщина изоляции мм |
Толщина оболочки мм |
Приблизительный наружный диаметр макс. мм |
Сопротивление проводника при 20°C Ом/км |
Приблизительный общий вес кг/км |
Макс. токовая нагрузка при 30°C Pipe A - Air A |
| 2 x 1 | 1,1 | 0,6 | 1,20 | 7 | 18,1 | 57 | 28 - 19 |
| 2 x 1,5 | 1,35 | 0,7 | 1,20 | 7,8 | 12,1 | 73 | 32 - 20 |
| 2 x 2,5 | 1,73 | 0,8 | 1,20 | 9,2 | 7,41 | 104 | 42 - 27 |
| 2 x 4 | 2,19 | 0,8 | 1,40 | 10,4 | 4,61 | 144 | 54 - 37 |
| 3 x 1 | 1,1 | 0,6 | 1,20 | 7,4 | 18,1 | 75 | 28 - 19 |
| 3 x 1,5 | 1,35 | 0,7 | 1,40 | 8,6 | 12,1 | 105 | 26 - 18 |
| 3 x 2,5 | 1,73 | 0,8 | 1,40 | 10,1 | 7,41 | 151 | 34 - 25 |
| 3 x 4 | 2,19 | 0,8 | 1,40 | 11 | 4,61 | 199 | 44 - 34 |
| 3 x 6 + 4 | 2,68 - 2,19 | 0,8 - 0,8 | 1,40 - 1,40 | 12,8 | 3,08 | 329 | 28 - 19 |
| 4 x 1,5 | 1,35 | 0,7 | 1,40 | 9,3 | 12,1 | 131 | 26 - 18 |
| 4 x 2,5 | 1,73 | 0,8 | 1,40 | 11 | 7,41 | 190 | 34 - 25 |
| 4 x 4 | 2,19 | 0,8 | 1,40 | 12 | 4,61 | 253 | 44 - 34 |
| 4 x 6 | 2,68 | 0,8 | 1,40 | 13,4 | 3,08 | 348 | 56 - 43 |
| 5 x 1,5 | 1,35 | 0,7 | 1,40 | 10,1 | 12,1 | 157 | 32 - 18 |
| 5 x 2,5 | 1,73 | 0,8 | 1,40 | 12 | 7,41 | 229 | 42 - 25 |
CBT cable is suitable for use in damp environments where there is no mechanical stress, including residential buildings, apartments, offices, and commercial premises. It is commonly used in both concealed and surface-mounted electrical installations.
It is widely used for lighting circuits, socket installations, fixed electrical connections, and indoor power distribution systems, providing safe and reliable power transmission.
| Nominal Kesit No x mm² |
İletken Çapı mm |
Standart Et Kalınlığı (İzole) mm |
Standart Et Kalınlığı (Kılıf) mm |
Yaklaşık Dış Çap max. mm |
20°C'de Maks. İletken DC Direnci Ω/km |
Yaklaşık Toplam Ağırlık kg/km |
30°C'de Maks. Akım Taşıma Kapasitesi Pipe A - Air A |
|---|---|---|---|---|---|---|---|
| Num. of Cores No x mm² |
Wires Diameter mm |
Thickness of Insulation mm |
Thickness of Sheath mm |
Approx. Overall Diameter max. mm |
Conductor DC Resistance at 20°C Ω/km |
Approx. Total Weight kg/km |
Max. Current Carrying Capacity at 30°C Pipe A - Air A |
| Номинальное сечение No x мм² |
Диаметр жилы мм |
Толщина изоляции мм |
Толщина оболочки мм |
Приблизительный наружный диаметр макс. мм |
Сопротивление проводника при 20°C Ом/км |
Приблизительный общий вес кг/км |
Макс. токовая нагрузка при 30°C Pipe A - Air A |
| 2 x 1 | 1,1 | 0,6 | 1,20 | 7 | 18,1 | 57 | 28 - 19 |
| 2 x 1,5 | 1,35 | 0,7 | 1,20 | 7,8 | 12,1 | 73 | 32 - 20 |
| 2 x 2,5 | 1,73 | 0,8 | 1,20 | 9,2 | 7,41 | 104 | 42 - 27 |
| 2 x 4 | 2,19 | 0,8 | 1,40 | 10,4 | 4,61 | 144 | 54 - 37 |
| 3 x 1 | 1,1 | 0,6 | 1,20 | 7,4 | 18,1 | 75 | 28 - 19 |
| 3 x 1,5 | 1,35 | 0,7 | 1,40 | 8,6 | 12,1 | 105 | 26 - 18 |
| 3 x 2,5 | 1,73 | 0,8 | 1,40 | 10,1 | 7,41 | 151 | 34 - 25 |
| 3 x 4 | 2,19 | 0,8 | 1,40 | 11 | 4,61 | 199 | 44 - 34 |
| 3 x 6 + 4 | 2,68 - 2,19 | 0,8 - 0,8 | 1,40 - 1,40 | 12,8 | 3,08 | 329 | 28 - 19 |
| 4 x 1,5 | 1,35 | 0,7 | 1,40 | 9,3 | 12,1 | 131 | 26 - 18 |
| 4 x 2,5 | 1,73 | 0,8 | 1,40 | 11 | 7,41 | 190 | 34 - 25 |
| 4 x 4 | 2,19 | 0,8 | 1,40 | 12 | 4,61 | 253 | 44 - 34 |
| 4 x 6 | 2,68 | 0,8 | 1,40 | 13,4 | 3,08 | 348 | 56 - 43 |
| 5 x 1,5 | 1,35 | 0,7 | 1,40 | 10,1 | 12,1 | 157 | 32 - 18 |
| 5 x 2,5 | 1,73 | 0,8 | 1,40 | 12 | 7,41 | 229 | 42 - 25 |
| Nominal Kesit No x mm² |
İletken Çapı mm |
Standart Et Kalınlığı (İzole) mm |
Standart Et Kalınlığı (Kılıf) mm |
Yaklaşık Dış Çap max. mm |
20°C'de Maks. İletken DC Direnci Ω/km |
Yaklaşık Toplam Ağırlık kg/km |
30°C'de Maks. Akım Taşıma Kapasitesi Pipe A - Air A |
|---|---|---|---|---|---|---|---|
| Num. of Cores No x mm² |
Wires Diameter mm |
Thickness of Insulation mm |
Thickness of Sheath mm |
Approx. Overall Diameter max. mm |
Conductor DC Resistance at 20°C Ω/km |
Approx. Total Weight kg/km |
Max. Current Carrying Capacity at 30°C Pipe A - Air A |
| Номинальное сечение No x мм² |
Диаметр жилы мм |
Толщина изоляции мм |
Толщина оболочки мм |
Приблизительный наружный диаметр макс. мм |
Сопротивление проводника при 20°C Ом/км |
Приблизительный общий вес кг/км |
Макс. токовая нагрузка при 30°C Pipe A - Air A |
| 2 x 1 | 1,1 | 0,6 | 1,20 | 7 | 18,1 | 57 | 28 - 19 |
| 2 x 1,5 | 1,35 | 0,7 | 1,20 | 7,8 | 12,1 | 73 | 32 - 20 |
| 2 x 2,5 | 1,73 | 0,8 | 1,20 | 9,2 | 7,41 | 104 | 42 - 27 |
| 2 x 4 | 2,19 | 0,8 | 1,40 | 10,4 | 4,61 | 144 | 54 - 37 |
| 3 x 1 | 1,1 | 0,6 | 1,20 | 7,4 | 18,1 | 75 | 28 - 19 |
| 3 x 1,5 | 1,35 | 0,7 | 1,40 | 8,6 | 12,1 | 105 | 26 - 18 |
| 3 x 2,5 | 1,73 | 0,8 | 1,40 | 10,1 | 7,41 | 151 | 34 - 25 |
| 3 x 4 | 2,19 | 0,8 | 1,40 | 11 | 4,61 | 199 | 44 - 34 |
| 3 x 6 + 4 | 2,68 - 2,19 | 0,8 - 0,8 | 1,40 - 1,40 | 12,8 | 3,08 | 329 | 28 - 19 |
| 4 x 1,5 | 1,35 | 0,7 | 1,40 | 9,3 | 12,1 | 131 | 26 - 18 |
| 4 x 2,5 | 1,73 | 0,8 | 1,40 | 11 | 7,41 | 190 | 34 - 25 |
| 4 x 4 | 2,19 | 0,8 | 1,40 | 12 | 4,61 | 253 | 44 - 34 |
| 4 x 6 | 2,68 | 0,8 | 1,40 | 13,4 | 3,08 | 348 | 56 - 43 |
| 5 x 1,5 | 1,35 | 0,7 | 1,40 | 10,1 | 12,1 | 157 | 32 - 18 |
| 5 x 2,5 | 1,73 | 0,8 | 1,40 | 12 | 7,41 | 229 | 42 - 25 |
Find answers to the most frequently asked questions about Avron Cable CBT Cable, including its applications, technical specifications, PVC-insulated construction, temperature resistance, and indoor electrical installation uses.